Accurate and reduced SISO Sequence Impedance Models of Grid-tied Voltage Source Converter for Small Signal Stability Analysis

Published 13 Apr 2017 in cs.SY | (1704.04157v1)

Abstract: Impedance models are widely used in assessing small signal stability of grid-tied voltage source converter (VSC) systems. Recent research has proven that impedance models of grid-tied VSC in both dq and sequence domains are generally Multi-Input Multi-Output (MIMO) systems, and the generalized Nyquist criterion has to be applied for stability analysis to these MIMO systems. However, finding Single-Input and Single-Output (SISO) equivalents for this system is always appealing because of the simplicity and the convenience for physical interpretation when assessing the stability, compared to MIMO systems. This paper presents two types of SISO impedance models of grid-tied VSC system, one is derived from the strong grid assumption, and the other is from the closed-loop equivalence. The accuracy of these models is assessed with respect to the measured impedances in PSCAD/EMTDC, and their effects on the stability assessment were analyzed as well. It is proven that the accurate SISO model gives identical result as the MIMO (matrix-based) impedance model with respect to stability analysis. However, the reduced SISO model may lead to wrong results if the bandwidth of phase locked loop is large.

Summary

Whiteboard

No one has generated a whiteboard explanation for this paper yet.

Open Problems

We haven't generated a list of open problems mentioned in this paper yet.

Continue Learning

We haven't generated follow-up questions for this paper yet.

Collections

Sign up for free to add this paper to one or more collections.